Wire Chart and Voltage Loss in Ohms per ft. (uncoated)

Use this chart for an exact figure     Use the voltage specific charts for quick reference

Single phase AC & DC current resistance at 75C 3-Phase AC in PVC conduit
AWG Copper Aluminum Copper Aluminum
14 0.0031 0.0027
12 0.00195 0.0017
10 0.00122 0.00202 0.0011 0.0018
8 0.00077 0.00127 0.00069 0.0011
6 0.000491 0.000808 0.00044 0.00071
4 0.000308 0.000508 0.00029 0.00046
2 0.000194 0.000319 0.00019 0.0003
1 0.000154 0.000253 0.00016 0.00024
1/0 0.000122 0.000201 0.00013 0.00019
2/0 0.0000967 0.000159 0.00011 0.00016
3/0 0.0000766 0.000126 0.000088 0.00013
4/0 0.0000608 0.0001 0.000074 0.00011

To find voltage Drop: Ohms per ft. X Wire Length X Hydro amps

Example: 200 ft. 6 gauge. Copper wire (100 ft. transmission) at 8 amps

200 X 0.000491 X 8   =   0.786   volts drop

To find hydro voltage:add voltage drop to battery voltage

12.6 +0.786 = 13.346 volts

To find % wire loss from above: Voltage drop from above / hydro voltage

0.786 /  13.346   =   .0589

5.89% for the total wire run, two conductors, each conductor is half.

Electrical inspectors would like to see 2% or less voltage loss per conductor. The Permanent magnet hydro is a dynamic power source that works outside of the usual concerns for motors and other types of generating equipment. The 2% rule is not relevant to the equipment. Most conductors available are rated for temp rise at 2000 volts to 75 C. We can easily waste 20% of the power being generated in each conductor on some of these long wire runs and still not detect any temperature gain at these low voltages. This would result in a drop in efficiency of 36% which is clearly unacceptable except for the longest of wire runs. Sometimes it is about what is possible and not what would be correct. As a rule I rarely will design a system with over 10% wire loss per conductor because there is usually some other option. You can either heat wire or charge the battery. Explore producing at a higher voltage and use a step down transformer/rectifier unit to reduce wire costs.

10% loss example: Hydro 12 amps @ 13.86 volts = 166.32 watts

Battery 12 amps @ 12.6 volts = 151.2 watts

2% loss example: Hydro 12.94 amps @ 12.853… volts = 166.32 watts

Battery 12.94 amps @ 12.6 volts = 163 watts

Quite often the hydro will also increase in efficiency providing another slight gain.

12 Volt DC

The following table shows the maximum transmission distance using copper wire assuming 2 volts drop total. This works out to a little less than 7% loss per conductor or just under 14% total voltage loss for the transmission distance. This is my personal limit for a 12 volt system which is naturally inefficient due to the low voltage. The table also assumes that the battery voltage is approximately 12.6 and the hydro voltage will be approximately 14.6 at the power level indicated. For 2% loss per conductor, the transmission distance will be 30% of the number in the column.

Wire gauge 14 12 10 8 6 4 2 1 1/0 2/0 3/0 4/0
5a/73w 62 100 160 250 400 625 1000 1250 1600 2000 2500 3200
10a/146w 31 50 80 125 200 312 500 625 800 1000 1250 1600
15a/219w 21 33 53 83 133 208 333 417 533 667 833 1067
20a/292w —– 25 40 62 100 156 250 312 400 500 625 800
25a/365w —– —– 32 50 80 125 200 250 320 400 500 640
30a/438w —– —– 27 42 67 104 167 208 267 333 417 533
35a/511w —– —– —– 36 58 91 146 181 233 291 364 466
40a/584w —– —– —– 31 50 78 125 156 200 250 312 400
45a/657w —– —– —– 25 45 70 110 140 180 225 281 360
50a/730w —– —– —– —– 40 62 100 125 160 200 250 320
60a/876w —– —– —– —– 33 52 83 104 133 166 208 266
70a/1022w —– —– —– —– —– 45 73 90 116 145 182 233
80a/1168w —– —– —– —– —– 39 62 78 100 125 156 200
90a/1314w —– —– —– —– —– —– 55 70 90 112 140 180
100a/1460w —– —– —– —– —– —– 50 62 80 100 125 160
125a/1825w —– —– —– —– —– —– —– 50 64 80 100 128
150a/2190w —– —– —– —– —– —– —– —– 53 67 83 107
175a/2555w —– —– —– —– —– —– —– —– 46 58 72 93
200a/2920w —– —– —– —– —– —– —– —– —– 50 62 80

24 Volt DC

The following table shows the maximum transmission distance using copper wire assuming 2.8 volts drop total. This works out to 5% loss per conductor or 10% total loss for the transmission distance. The table also assumes that the battery voltage is approx. 25.2 and the hydro voltage is 28.0 at the power level indicated. 2% conductor loss is 40% of the number in the column.

Wire gauge 14 12 10 8 6 4 2 1 1/0 2/0 3/0 4/0
5a/140w 87 140 224 350 560 875 1400 1750 2240 2800 3500 4480
10a/280w 43 70 112 175 280 437 700 875 1120 1400 1750 2240
15a/420w 29 47 73 117 187 292 467 583 747 933 1167 1493
20a/560w —- 35 56 87 140 218 350 437 560 700 875 1120
25a/700w —- —- 45 70 112 175 280 350 448 560 700 896
30a/840w —- —- 37 59 94 146 234 292 374 467 584 747
35a/960w —- —- —- 50 80 125 200 250 320 400 500 640
40a/1120w —- —- —- 43 70 109 175 218 280 350 437 560
45a/1260w —- —- —- 39 62 97 155 194 249 311 389 498
50a/1400w —- —- —- —- 56 87 140 175 224 280 350 448
60a/1680w —- —- —- —- 47 73 117 146 187 233 292 373
70a/1920w —- —- —- —- —- 62 100 125 160 200 250 320
80a/2240w —- —- —- —- —- 54 87 109 140 175 218 280
90a/2520w —- —- —- —- —- —- 77 97 124 155 194 249
100a/2800w —- —- —- —- —- —- 70 87 112 140 175 224
125a/3500w —- —- —- —- —- —- —- 70 89 112 140 179
150a/4200w —- —- —- —- —- —- —- —- 75 93 117 149
175a/4900w —- —- —- —- —- —- —- —- 66 81 102 130
200a/5600w —- —- —- —- —- —- —- —- —- 70 87 112

32 Volt DC

Still in limited use, the equipment used is primarily remnants of the marine industry. It was also the old standard for rural electrification and telegraph up to the 1950’s and military applications prior to WW2 in the U.S. This chart is being shown to accommodate Nickel Iron batteries on a 24 volt system to more accurately size the hydro wiring which is gaining in popularity. Personally I don’t care for the efficiency of the Nickel Iron battery and I encourage you to dig into the issue before implementing them. Read the section on Nickel Iron batteries for more information. The following table shows the maximum transmission distance using copper wire assuming 3.32 volts drop total. This works out to 5% loss per conductor or 10% loss for the transmission distance. The table also assumes the battery voltage is approximately 33.2 and the hydro voltage is 36.52 at the power level indicated. 2% conductor loss is 40% of the number in the column.

Wire gauge 14 12 10 8 6 4 2 1 1/0 2/0 3/0 4/0
5a/183w 103 166 266 415 664 1037 1660 2076 2657 3321 4151 5313
10a/365w 51 83 133 207 332 518 830 1038 1328 1660 2075 2656
15a/548w 34 55 89 138 221 346 553 692 886 1107 1384 1771
20a/730w —- 42 67 104 166 259 415 519 664 830 1038 1328
30a/1095w —- —- 44 69 110 173 276 346 443 553 692 885
40a/1460w —- —- —- 52 83 129 207 259 332 415 519 664
50a/1825w —- —- —- —- 66 104 166 208 266 332 415 531
60a/2190w —- —- —- —- 55 86 138 173 221 276 346 442
80a/2920w —- —- —- —- —- 64 103 129 166 207 259 332
100a/3650w —- —- —- —- —- —- 83 104 133 166 207 265

48 Volt DC

The following table shows the maximum transmission distance using copper wire assuming 5.6 volts drop total. This works out to 5% loss per conductor or 10% total voltage loss for the transmission distance. The table also assumes that the battery voltage is approximately 50.4 and the hydro voltage is 56.0 at the power level indicated. 2% conductor loss is 40% of the distance listed.

Wire gauge 14 12 10 8 6 4 2 1 1/0 2/0 3/0 4/0
5a/280w 175 280 448 700 1120 1750 2800 3500 4480 5600 7000 8960
10a/560w 86 140 224 350 560 875 1400 1750 2240 2800 3500 4480
15a/840w 58 94 146 235 375 584 935 1166 1495 1866 2333 2986
20a/1120w —- 70 112 175 280 437 700 875 1120 1400 1750 2240
25a/1400w —- —- 90 140 224 350 560 700 896 1120 1400 1792
30a/1680w —- —- 73 117 187 292 467 583 747 933 1167 1493
35a/1960w —- —- —- 100 160 250 400 500 640 800 1000 1280
40a/2240w —- —- —- 87 140 218 350 437 560 700 875 1120
45a/2520w —- —- —- 78 124 194 310 388 498 622 778 996
50a/2800w —- —- —- —- 112 175 280 350 448 560 700 896
60a/3360w —- —- —- —- 94 146 234 292 374 467 584 747
70a/3920w —- —- —- —- —- 124 200 250 320 400 500 640
80a/4480w —- —- —- —- —- 108 175 218 280 350 437 560
90a/5040w —- —- —- —- —- —- 154 194 249 311 389 498
100a/5600w —- —- —- —- —- —- 140 175 224 280 350 448
125a/7000w —- —- —- —- —- —- —- 140 178 224 280 358
150a/8400w —- —- —- —- —- —- —- —- 150 186 234 298
175a/9600w —- —- —- —- —- —- —- —- 132 162 204 266
200a/11200w —- —- —- —- —- —- —- —- —- 140 174 224

62 Volt DC

This table is for sizing the maximum distance of the hydro wire run in a nominal 48 volt Nickel Iron battery system using copper wire assuming 6.2 volts drop total. This works out to 5% loss per conductor or 10% total voltage loss for the transmission distance. The table also assumes that the battery voltage is approx. 62.0 and the hydro voltage is 68.2 at the power level indicated. 2% conductor loss is 40% of the distance listed. Read the section on Nickel Iron batteries for more information. The table is also useful as one of the voltages commonly found by the MPPT controllers.

Wire gauge 14 12 10 8 6 4 2 1 1/0 2/0 3/0 4/0
5a/341w 193 308 493 770 1232 1925 3080 3850 4928 6150 7700 9856
10a/682w 96 154 246 385 616 862 1540 1925 2464 3075 3850 4928
15a/1023w 64 103 164 257 411 642 1027 1283 1643 2050 2567 3285
20a/1364w —- 77 123 192 308 431 770 962 1232 1537 1925 2464
30a/2046w —- —- 82 128 205 321 513 641 821 1025 1283 1642
40a/2728w —- —- —- 96 154 215 385 481 616 768 962 1232
50a/3410w —- —- —- —- 123 192 308 385 493 615 770 986
60a/4092w —- —- —- —- 102 160 256 320 410 512 641 821

75 Volt DC

This Table is strictly for figuring the maximum distance hydro wire run at a voltage commonly found by some of the MPPT controllers using copper wire assuming 7.5 volts drop total. This works out to 5% loss per conductor or 10% total voltage loss for the transmission distance. The table is built to reflect 75 volts at the controller and 82.5 at the hydro. This table can be used at any voltage if you scale the numbers by percentage. That includes the watt figure as well. An increase of 10% on voltage will yield 10% longer distance and vice versa. The voltage drop also changes proportionally. 2% loss per conductor is 40% of the distance in the column. Read the section on MPPT controllers

Wire gauge 14 12 10 8 6 4 2 1 1/0 2/0 3/0 4/0
5a/412w 234 375 600 938 1500 2343 3750 4688 6000 7500 9375 —-
10a/824w 117 187 300 469 750 1172 1875 2344 3000 3750 4687 6000
15a/1236w 78 125 200 313 500 781 1250 1563 2000 2500 3125 4000
20a/1648w —- 93 150 234 375 586 937 1172 1500 1875 2344 3000
30a/2472w —- —- 100 156 250 370 625 781 1000 1250 1562 2000
40a/3296w —- —- —- 117 187 293 468 586 750 937 1172 1500
50a/4120w —- —- —- —- 150 234 375 469 600 750 938 1200
60a/4944w —- —- —- —- 125 185 312 390 500 625 781 1000

120 Volt DC

The following table shows the maximum transmission distance using copper wire assuming 9.6 volts drop total. The 120 VDC system is used extensively around the world but is effectively outlawed in the US. Fear and misunderstanding from the people entrusted with over-protecting us? A pretty silly idea considering they allow Solar systems operating close to 1000VDC. The table assumes 4% loss per conductor or 8% voltage loss total. 2% is 50% of the distance listed. This table also shows the highest MPPT voltage generally found by the Midnight 250. We can also build a step down TR/rect. unit from a higher voltage to 120 VDC to help reduce wire costs.

Wire gauge 14 12 10 8 6 4 2 1 1/0 2/0
1a/128w 1500 2400 3840 6000 9600    —-    —-    —-    —-    —-
2a/256w 750 1200 1920 3000 4800 7500    —-    —-    —-    —-
3a/384w 500 800 1280 2000 3200 5000 8000    —-    —-    —-
5a/640w 300 480 768 1200 1920 3000 4800 6000 7680 9600
10a/1280w 150 240 384 600 960 1500 2400 3000 3840 4800
15a/1920w 100 160 256 400 640 1000 1600 2000 2560 3200
20a/2560w —- 120 192 300 480 750 1200 1500 1920 2400
25a/3200w. —- —- 154 240 384 600 960 1200 1536 1920
30a/3840w —- —- 128 200 320 500 800 1000 1280 1600
35a/4480w —- —- —- 172 274 429 686 857 1097 1371
40a/5120w —- —- —- 150 240 375 600 750 960 1200
50a/6400w —- —- —- —- 192 300 480 600 768 960
60a/7680w —- —- —- —- 160 250 400 500 640 800

DC transmission versus AC transmission

The biggest exaggeration ever told in the electrical world and repeated until accepted as fact might be: “AC travels further than DC “………well….OK. Reactive capacitance can change the effective wire loss in some 3-phase AC circuits which is applicable to some of our 3-phase wild PM units but otherwise…

NO

The truth should go something like this: AC travels slightly further than DC under certain circumstances and it is easier and more economical to transform into usable AC and DC power at the point of use. AC is more commonly found at the higher voltage levels and is easier to produce at those voltage levels.

Figuring Single Phase AC current per conductor

Watts/Volts=Amps and then, Amps/Power factor=current per conductor

1400 watts/200 volts = 7 amps, 7 amps/0.85 PF= 0.824 amps

Most of the time the power factor is at or close to 1.0 however.

120 Volt AC single phase

For use with our PM 1032 hydro up to 800 watts either direct load resistive heating or incandescent lighting at fixed load and water volume or to a step down transformer rectifier unit for battery charging. These are less efficient that our 3-phase models but makes two wire transmission possible. This table can also be used for conventional AC hydro wire sizing at 120 volt 60Hz. The table assumes the conductors are copper and allows 4% loss per conductor or 8% loss for the transmission distance. 2% loss is 50% of the distance listed. Inherently regulated AC generators will need to be within the 2% range for proper operation.

Wire gauge 14 12 10 8 6 4 2 1 1/0 2/0 3/0 4/0
100w 1920 3072 4914 7680    —-    —-    —-    —-    —-    —-    —-    —-
200w 960 1536 2457 3840 6144 9600    —-    —-    —-    —-    —-    —-
300w 640 1024 1628 2560 4096 6400    —-    —-    —-    —-    —-    —-
400w 480 768 1228 1920 3072 4800 7680 9600    —-    —-    —-    —-
500w 384 614 983 1536 2458 3840 6144 7680 9808    —-    —-    —-
600w 320 512 819 1280 2048 3200 5120 6400 8190    —-    —-    —-
800w 240 384 614 960 1536 2400 3840 4800 6141 7680 9600    —-
1000w 192 307 481 768 1229 1920 3072 3840 4814 6144 7680 9825
1200w 160 256 410 640 1024 1600 2560 3200 4095 5120 6400 8188
1500w 128 205 328 512 819 1280 2048 2893 3276 4096 5120 6550
1800w 107 172 274 428 686 1072 1715 2144 2743 3430 4288 5485
2100w —– 146 234 366 585 914 1462 1829 2340 2926 3657 4679
2400w —– 128 205 320 512 800 1280 1600 2047 2560 3200 4094
2700w —– 114 181 284 455 711 1140 1422 1820 2276 2844 3639
3000w —– —– 163 256 410 640 1024 1280 1638 2048 2560 3275
3500w —– —– 140 219 351 548 878 1097 1404 1755 2194 2807
4000w —– —– 123 192 307 480 768 960 1228 1536 1919 2456
4500w —– —– —– 171 273 427 683 853 1092 1365 1706 2183
5000w —– —– —– 154 246 384 614 768 983 1229 1536 1838

240 Volt AC Single Phase

Same as above except 240 volt. 4X the distance or 4X the power of 120 volt

Wire gauge 14 12 10 8 6 4 2 1 1/0 2/0 3/0 4/0
100w 7680 12288 18856 30720 —– —– —– —– —– —– —– —–
200w 3840 6144 9428 15360 22580 —– —– —– —– —– —– —–
300w 2560 4090 6410 10240 16390 25600 —– —– —– —– —– —–
500w 1536 2456 3928 6144 9032 15360 24576 —– —– —– —– —–
750w 1024 1638 2620 4096 6020 10240 16384 20480 26154 —– —– —–
1000w 768 1228 1964 3072 4516 7680 12288 15360 19616 24576 —– —–
1500w 512 819 1310 2048 3010 5120 8192 10240 13077 16384 20480 26200
2000w 384 614 983 1536 2258 3840 6144 7680 9808 12288 15360 19650
2500w 307 492 786 1228 1806 3072 4916 6144 7702 9830 12288 15720
3000w 256 409 641 1024 1639 2560 4096 5120 6419 8192 10240 13100
3500w 219 351 549 877 1404 2194 3511 4389 5502 7022 8777 11229
4000w —– 307 481 768 1229 1920 3072 3840 4814 6144 7680 9825
5000w —– 246 393 614 903 1536 2458 3072 3851 4915 6144 7860
6000w —– —– 320 512 820 1280 2048 2560 3210 4096 5120 6550
7000w —– —– 274 439 702 1097 1755 2194 2756 3511 4388 5615
8000w —– —– 240 384 614 960 1536 1920 2407 3072 3840 4912
10Kw —– —– —– 307 452 768 1229 1536 1962 2458 3072 3930
15Kw —– —– —– —– 301 512 819 1024 1308 1638 2048 2620
20Kw —– —– —– —– —– 384 614 768 981 1229 1536 1965

480 Volt Single Phase

Same as above except 480 volt. 4X the distance or 4X the power of 240 volt

Wire gauge 14 12 10 8 6 4 2 1 1/0 2/0 3/0 4/0
100w 30700 —– —– —– —– —– —– —– —– —– —– —–
200w 15360 24560 —– —– —– —– —– —– —– —– —– —–
300w 10240 16380 26200 —– —– —– —– —– —– —– —– —–
500w 6140 9840 15720 24560 —– —– —– —– —– —– —– —–
750w 4096 6552 10480 16384 24080 —– —– —– —– —– —– —–
1000w 3070 4920 7860 12280 18060 30720 —– —– —– —– —– —–
1500w 2048 3276 5240 8192 12040 20480 —– —– —– —– —– —–
2000w 1536 2456 3928 6144 9032 15360 24576 —– —– —– —– —–
2500w 1228 1968 3144 4912 7224 12288 19664 24576 —– —– —– —–
3000w 1024 1638 2620 4096 6020 10240 16384 20480 26154 —– —– —–
3500w 878 1404 2246 3510 5162 8778 14044 17554 22418 27950 —– —–
4000w 768 1228 1964 3072 4516 7680 12288 15360 19616 24576 —— —–
5000w 614 984 1572 2456 3612 6144 9832 12288 15404 19660 24576 —–
6000w 512 819 1310 2048 3010 5120 8192 10240 13077 16384 20480 26200
7000w 439 702 1123 1755 2581 4389 7022 8777 11209 13975 17554 22457
8000w —– 614 983 1536 2258 3840 6144 7680 9808 12288 15360 19650
10Kw —– 492 786 1228 1806 3072 4916 6144 7702 9830 12288 15720
15Kw —– —– 524 819 1204 2048 3277 4076 5135 6553 8192 10480
20Kw —– —– —- 614 903 1536 2458 3072 3851 4915 6144 7860

Figuring 3-Phase AC current per conductor
Watts/Line-to-line voltage X 0.667 = current per conductor. The range is 0.61 to 0.71 depending on head and volume of the water source and resultant operating frequency (PF). There are so many variables involved with wild frequency and the math is not simple, that this guide is intended to show distances that are most likely only. Sites with less than 50 ft. of head should be reduced about 3%.

—–Caution—-

The High voltage turbines should be installed inside some type of suitable dry and securable structure for safety reasons. We assume no liability for poor application of our products.

3-Phase 120 Volt 3 wire

This table is for use with our long distance transmission unrectified versions of Model PM 1800 and PM 2500 which is wild 3-phase. The frequency range is determined by head and volume but usually between 50 and 150 Hz. The voltage will also depend on battery state of charge after the TR/rect. unit. The voltage range will usually fall between 80 and 120 VAC line-to-line. Most will be around 100 VAC line-to-line and this table is built on that assumption. 120 volt 3-phase is unusual but some sites do not meet the rotational minimums to produce a higher voltage. The table assumes that the conductors are copper and in PVC conduit. The table also assumes 4% loss per conductor or 8% total voltage loss for the transmission distance at the power level indicated. When sizing wire for conventional AC generators, the distances can be increased by 20% depending on the type of generator to allow for the higher operating voltage. 2% conductor loss is 50% of the distance listed.

Wire gauge 14 12 10 8 6 4 2 1 1/0 2/0 3/0 4/0
100w 2320 3680 5640 9040 14160 21520 —– —– —– —– —– —–
200w 1160 1840 2820 4520 7080 10760 16420 19500 24000 28360 —– —–
300w 776 1224 1880 3016 4720 7176 10944 13000 16000 18904 23640 28104
400w 580 920 1410 2260 3540 5380 8210 9750 12000 14180 17730 21080
500w 464 736 1128 1808 2832 4304 6568 7800 9600 11344 14184 16864
600w 388 612 940 1508 2360 3588 5472 6500 8000 9452 11820 14052
800w 290 460 705 1130 1770 2690 4105 4875 6000 7090 8865 10540
1000w 232 368 564 904 1416 2152 3284 3900 4800 5672 7092 8432
1200w 194 306 470 754 1180 1794 2736 3250 4000 4726 5910 7026
1500w 156 244 376 604 944 1436 2188 2600 3200 3780 4728 5620
1800w 129 204 313 502 787 1196 1824 3167 2667 3151 3940 4684
2100w 111 175 268 430 675 1025 1563 2715 2286 2701 3377 4015
2400w 97 153 235 377 590 897 1368 1625 2000 2363 2955 3513
2700w 86 136 209 335 524 797 1216 1444 1777 2100 2627 3123
3000w 78 122 188 302 472 718 1094 1300 1600 1890 2364 2810
3500w —– 105 161 259 405 615 938 1114 1371 1620 2026 2409
4000w —– 92 141 226 354 538 821 975 1200 1418 1773 2108
4500w —– —– 125 201 315 478 730 867 1067 1260 1576 1874
5000w —– —– 113 181 283 430 657 780 960 1134 1418 1686

3-Phase 240 Volt AC 3 wire

Similar to 120 volt above except 240 VAC. The voltage range will usually fall between 160 and 240 VAC line-to-line. Most will be around 200 VAC line-to-line. All other assumptions are the same. Open circuit on these turbines can be 350-400VAC. 2% loss per conductor is 50% of the table distance.

4X the distance or 4X the power of 120 volt

Wire gauge 14 12 10 8 6 4 2 1 1/0 2/0 3/0 4/0
100w 9280 14720 22600 —— —— —— —– —– —– —– —– —–
200w 4640 7360 11280 18080 28320 —— —– —– —– —– —– —–
300w 3120 4880 7320 12080 18880 28720 —– —– —– —– —– —–
500w 1860 2960 4520 7240 11320 17200 26280 —– —– —– —– —–
750w 1248 1952 2928 4832 7552 11488 17504 20800 25600 —– —– —–
1000w 928 1472 2260 3620 5660 8600 13140 15600 19200 22680 28360 —–
1500w 624 976 1464 2416 3776 5744 8752 10400 12800 15120 18912 22480
2000w 464 736 1128 1808 2832 4304 6568 7800 9600 11344 14184 16864
2500w 372 592 904 1448 2264 3440 5256 6240 7680 9072 11344 13488
3000w 312 488 732 1208 1888 2872 4376 5200 6400 7560 9456 11240
3500w 267 418 627 1035 1618 2462 3571 4457 5486 6480 8105 9634
4000w 232 368 564 904 1416 2152 3284 3900 4800 5672 7092 8432
5000w —– 296 452 724 1132 1720 2628 3120 3840 4536 5672 6744
6000w —– 244 376 604 944 1436 2188 2600 3200 3780 4728 5620
7000w —– —– 313 517 809 1231 1785 2228 2743 3240 4052 4817
8000w —– —– 282 452 708 1076 1642 1950 2400 2836 3546 4216
10Kw —– —– 226 362 566 860 1314 1560 1920 2268 2836 3372
15Kw —– —– —– 242 378 574 875 1040 1280 1512 1891 2248
20Kw —– —– —– —– 283 430 657 780 960 1134 1418 1686

3-Phase 480 Volt AC 3 wire

Similar to the 240 units above except 480 volt. The voltage range will usually fall between 320 and 480 VAC line-to-line. Most will be around 400 VAC. All other assumptions are the same. Open circuit on these turbines can be 700-800 VAC and may require special wire. 2% is 50% of the table distance

4X the distance or 4X the power as 240 volt.

Wire gauge 14 12 10 8 6 4 2 1 1/0 2/0 3/0 4/0
100w 37200 —– —– —– —– —– —– —– —– —– —– —–
200w 18600 29600 —– —– —– —– —– —– —– —– —– —–
300w 12480 19520 29280 —— —– —– —– —– —– —– —– —–
500w 7440 11840 18080 28960 —– —– —– —– —– —– —– —–
750w 4992 7808 11712 19328 —– —– —– —– —– —– —– —–
1000w 3720 5920 9040 14480 22640 —– —– —– —– —– —– —–
1500w 2496 3904 5856 9664 15104 22976 —– —– —– —– —– —–
2000w 1860 2960 4520 7240 11320 17200 26280 —– —– —– —– —–
2500w 1488 2368 3616 5792 9056 13760 21024 24960 —– —– —– —–
3000w 1248 1952 2928 4832 7552 11488 17504 20800 25600 —– —– —–
3500w 1070 1673 2510 4142 6473 9847 15003 17829 21943 25920 —– —–
4000w 928 1472 2260 3620 5660 8600 13140 15600 19200 22680 28360 —–
5000w 744 1184 1808 2896 4528 6880 10512 12480 15360 18144 22688 26976
6000w 624 976 1464 2416 3776 5744 8752 10400 12800 15120 18912 22480
7000w 535 836 1255 2071 3236 4923 7501 8914 10971 12960 16210 19269
8000w 464 736 1128 1808 2832 4304 6568 7800 9600 11344 14184 16864
10Kw 372 592 904 1448 2264 3440 5256 6240 7680 9072 11344 13488
15Kw —– 390 586 966 1510 2298 3501 4160 5120 6048 7564 8992
20Kw —– —– 452 724 1132 1720 2628 3120 3840 4536 5672 6744